Need help?

THE-MP M 150 MM

Application

Final filtration in air handling units for “CLEANROOM” application

Application areas

  • Consists of mini-pleat media that replaces the old generation deep pleat media
  • High air flow rate
  • Low pressure drop
  • Individual leak test of 0.3 µm at 0.45 m/s according to DIN 24.184 (from H13)
  • Individual MPPS efficiency test of 0.12 µm at 0.45 m/s (scanning test) according to EN182 standard
  • Individual test certificate (scanning test) provided with the filter
  • Double labeling for traceability
  • Tested for food contact according to CE 1935/2004
  • Certified inert to microbial growth (ISO 846-VDI 6022)
Certificates

General Characteristics

Filtration class EN1822: E10-H14
Media: mini-pleat glass fiber paper
Frame: MDF (M)
Seal: polyurethane half-round monobloc
Separators: continuous thermoplastic wires
Seal: polyurethane half-round monobloc
Final pressure drop: 600 Pa
Maximum continuous service temperature: 70°C
Relative humidity: 70-80%
Contact our expert
  • THE-MP M 150 MM

    Illustration variation
  • E10

    • THE-MP100M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      3,1

    • Airflow (m3/h)/Delta P (Pa)

      850 / 250

    • THE-MP100M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      6,2

    • Airflow (m3/h)/Delta P (Pa)

      1700 / 250

    • THE-MP100M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      9,4

    • Airflow (m3/h)/Delta P (Pa)

      2550 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      12,5

    • Airflow (m3/h)/Delta P (Pa)

      3500 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      762

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      15,6

    • Airflow (m3/h)/Delta P (Pa)

      4250 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      18,7

    • Airflow (m3/h)/Delta P (Pa)

      5100 / 150

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      25

    • Airflow (m3/h)/Delta P (Pa)

      6800 / 250

    • THE-MP100M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      37,5

    • Airflow (m3/h)/Delta P (Pa)

      10200 / 250

    • THE-MP100M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      4,5

    • Airflow (m3/h)/Delta P (Pa)

      900 / 250

    • THE-MP100M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      9

    • Airflow (m3/h)/Delta P (Pa)

      1800 / 250

    • THE-MP100M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      13,5

    • Airflow (m3/h)/Delta P (Pa)

      2700 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      18

    • Airflow (m3/h)/Delta P (Pa)

      3600 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      762

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      22,5

    • Airflow (m3/h)/Delta P (Pa)

      4500 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      27

    • Airflow (m3/h)/Delta P (Pa)

      5400 / 250

    • THE-MP100M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      36

    • Airflow (m3/h)/Delta P (Pa)

      7200 / 250

    • THE-MP100M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      54

    • Airflow (m3/h)/Delta P (Pa)

      10800 / 250

  • H13

    • THE-MP130M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      3,1

    • Airflow (m3/h)/Delta P (Pa)

      475 / 250

    • THE-MP130M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      6,2

    • Airflow (m3/h)/Delta P (Pa)

      750 / 250

    • THE-MP130M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      9,4

    • Airflow (m3/h)/Delta P (Pa)

      1120 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      12,5

    • Airflow (m3/h)/Delta P (Pa)

      1500 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      762

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      15,6

    • Airflow (m3/h)/Delta P (Pa)

      1870 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      18,7

    • Airflow (m3/h)/Delta P (Pa)

      2250 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      25

    • Airflow (m3/h)/Delta P (Pa)

      3000 / 250

    • THE-MP130M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      37,5

    • Airflow (m3/h)/Delta P (Pa)

      4500 / 250

    • THE-MP130M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      4,5

    • Airflow (m3/h)/Delta P (Pa)

      475 / 250

    • THE-MP130M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      9

    • Airflow (m3/h)/Delta P (Pa)

      950 / 250

    • THE-MP130M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      13,5

    • Airflow (m3/h)/Delta P (Pa)

      1420 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      18

    • Airflow (m3/h)/Delta P (Pa)

      1900 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      27

    • Airflow (m3/h)/Delta P (Pa)

      2850 / 250

    • THE-MP130M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      36

    • Airflow (m3/h)/Delta P (Pa)

      3800 / 250

    • THE-MP130M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      54

    • Airflow (m3/h)/Delta P (Pa)

      5700 / 250

  • H14

    • THE-MP140M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      3,1

    • Airflow (m3/h)/Delta P (Pa)

      325 / 250

    • THE-MP140M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      6,2

    • Airflow (m3/h)/Delta P (Pa)

      650 / 250

    • THE-MP140M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      9,4

    • Airflow (m3/h)/Delta P (Pa)

      975 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      12,5

    • Airflow (m3/h)/Delta P (Pa)

      1300 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      762

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      15,6

    • Airflow (m3/h)/Delta P (Pa)

      1620 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      18,7

    • Airflow (m3/h)/Delta P (Pa)

      1950 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      25

    • Airflow (m3/h)/Delta P (Pa)

      2600 / 250

    • THE-MP140M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      75

    • Surface (m2)

      37,5

    • Airflow (m3/h)/Delta P (Pa)

      3900 / 250

    • THE-MP140M

    • Base A (mm)

      305

    • Height B (mm)

      305

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      4,5

    • Airflow (m3/h)/Delta P (Pa)

      400 / 250

    • THE-MP140M

    • Base A (mm)

      305

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      9

    • Airflow (m3/h)/Delta P (Pa)

      800 / 250

    • THE-MP140M

    • Base A (mm)

      457

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      13,5

    • Airflow (m3/h)/Delta P (Pa)

      1200 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      610

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      18

    • Airflow (m3/h)/Delta P (Pa)

      1600 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      762

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      22,5

    • Airflow (m3/h)/Delta P (Pa)

      2000 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      915

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      27

    • Airflow (m3/h)/Delta P (Pa)

      2400 / 250

    • THE-MP140M

    • Base A (mm)

      610

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      36

    • Airflow (m3/h)/Delta P (Pa)

      3200 / 250

    • THE-MP140M

    • Base A (mm)

      915

    • Height B (mm)

      1220

    • Thickness C (mm)

      150

    • Filter pack (mm)

      100

    • Surface (m2)

      54

    • Airflow (m3/h)/Delta P (Pa)

      4800 / 250

* Energy consumption, kWh/year: calculated according to Eurovent Guideline 4/21-2018 | ** Energy class: according to Eurovent RS4/C/001-2019 | *** Energy class: according to Eurovent RS4/C/001-2015
Application areas

An air filtration system adapted to each sector

Illustration

Pharmaceutical Industry

Air filters ensuring safety adapted to pharmaceutical industry procedures

Discover all sectors
TFM® Service

Choose TFM® and benefit from a comprehensive maintenance contract for air filtration.

Need clean air in your workplace? With the TFM® contract, you will benefit from high-performance air filters tailored to your needs, scalable services, and dedicated teams to advise you on the installation of new equipment.

Learn more about our service

Do you have any questions? Our team is here to help.

Our experts are available to answer all your questions.

Contact our expert
Expert illustration

Hi, my name is Wannes Van Herck, how can I assist you?

Contact our expert